Measurement of air exchange rates in different indoor environments using continuous CO2 sensors | |
You, Yan ; Niu, Can ; Zhou, Jian ; Liu, Yating ; Bai, Zhipeng ; Zhang, Jiefeng ; He, Fei ; Zhang, Nan | |
刊名 | Environmental Sciences & Ecology |
2012 | |
卷号 | 24期号:4页码:657-664 |
关键词 | air exchange rate continuous CO2 sensor steady-state method decay method particulate matter indoor-outdoor concentration relationship |
ISSN号 | 1001-0742 |
中文摘要 | A new air exchange rate (AER) monitoring method using continuous CO2 sensors was developed and validated through both laboratory experiments and field studies. Controlled laboratory simulation tests were conducted in a 1-m(3) environmental chamber at different AERs (0.1-10.0 hr(-1)). AERs were determined using the decay method based on box model assumptions. Field tests were conducted in classrooms, dormitories, meeting rooms and apartments during 2-5 weekdays using CO2 sensors coupled with data loggers. Indoor temperature, relative humidity (RH), and CO2 concentrations were continuously monitored while outdoor parameters combined with on-site climate conditions were recorded. Statistical results indicated that good laboratory performance was achieved: duplicate precision was within 10%, and the measured AERs were 90%-120% of the real AERs. Average AERs were 1.22, 1.37, 1.10, 1.91 and 0.73 hr(-1) in dormitories, air-conditioned classrooms, classrooms with an air circulation cooling system, reading rooms, and meeting rooms, respectively. In an elderly particulate matter exposure study, all the homes had AER values ranging from 0.29 to 3.46 hr(-1) in fall, and 0.12 to 1.39 hr(-1) in winter with a median AER of 1.15. |
WOS记录号 | WOS:000303297400012 |
公开日期 | 2014-11-26 |
内容类型 | 期刊论文 |
源URL | [http://ir.rcees.ac.cn/handle/311016/8019] |
专题 | 生态环境研究中心_大气环境科学实验室 |
推荐引用方式 GB/T 7714 | You, Yan,Niu, Can,Zhou, Jian,et al. Measurement of air exchange rates in different indoor environments using continuous CO2 sensors[J]. Environmental Sciences & Ecology,2012,24(4):657-664. |
APA | You, Yan.,Niu, Can.,Zhou, Jian.,Liu, Yating.,Bai, Zhipeng.,...&Zhang, Nan.(2012).Measurement of air exchange rates in different indoor environments using continuous CO2 sensors.Environmental Sciences & Ecology,24(4),657-664. |
MLA | You, Yan,et al."Measurement of air exchange rates in different indoor environments using continuous CO2 sensors".Environmental Sciences & Ecology 24.4(2012):657-664. |