沼气热泵系统设计及其经济性分析 | |
吴集迎 | |
刊名 | http://epub.edu.cnki.net/grid2008/brief/detailj.aspx?filename=nyjx200612027&dbcode=CJFQ&dbname=CJFQ2006
![]() |
2012-06-05 ; 2012-06-05 | |
关键词 | 沼气 直燃型吸收式热泵 系统设计 经济性 Biogas Direct fired absorption heat pump System design Economy TU831.6 |
其他题名 | System Design and Economic Analysis of Absorption Heat Pump Driven by Biogas |
中文摘要 | 燃气直燃型吸收式热泵具有明显的节能环保特点。在目前能源紧张的情况下,如何利用沼气资源作为燃料驱动吸收式热泵,值得重视。结合直燃型吸收式热泵技术的最新研究进展,对沼气直燃型吸收式热泵进行系统设计及经济性分析。结果表明,直燃型吸收式热泵机组的一次能源利用率(PER)比活塞式、螺杆式及涡旋式热泵机组分别高14.1%、14.3%和6.8%,沼气热泵的节能效益更为显著。; Direct fired absorption heat pump (DFAHP) has great potentialities in energy saving and in environmental protection. Driven DFAHP by biogas became more and more important with the severe energy situation at present. The recent developments of absorption heat pump technology were introduced, the system design of DFAHP driven by biogas was developed, and the economic analysis was given out in the end. The results showed that the primary energy ratio (PER) of DFAHP was 14.1%,14.3% and 6.8% higher than that of compression heat pump which is driven by reciprocating compressor, screw compressor and scroll compressor respectively. The energy saving effect of DFAHP driven by biogas is much more significant.; 【作者单位】集美大学机械工程学院 副教授; 361021福建省厦门市;【作者英文名】Wu Jiying(Jimei University) |
语种 | 中文 |
内容类型 | 期刊论文 |
源URL | [http://ir.calis.edu.cn/hdl/235041/14309] ![]() |
专题 | 集美大学 |
推荐引用方式 GB/T 7714 | 吴集迎. 沼气热泵系统设计及其经济性分析[J]. http://epub.edu.cnki.net/grid2008/brief/detailj.aspx?filename=nyjx200612027&dbcode=CJFQ&dbname=CJFQ2006,2012, 2012. |
APA | 吴集迎.(2012).沼气热泵系统设计及其经济性分析.http://epub.edu.cnki.net/grid2008/brief/detailj.aspx?filename=nyjx200612027&dbcode=CJFQ&dbname=CJFQ2006. |
MLA | 吴集迎."沼气热泵系统设计及其经济性分析".http://epub.edu.cnki.net/grid2008/brief/detailj.aspx?filename=nyjx200612027&dbcode=CJFQ&dbname=CJFQ2006 (2012). |
个性服务 |
查看访问统计 |
相关权益政策 |
暂无数据 |
收藏/分享 |
除非特别说明,本系统中所有内容都受版权保护,并保留所有权利。
修改评论