An improved OPA model and the evaluation of blackout risk | |
Mei Shengwei ; He Fei ; Zhang Xuemin ; Xia Deming | |
2010-10-12 ; 2010-10-12 | |
关键词 | Practical/ power grids power system control power system simulation/ OPA model blackout risk inner iteration power flow power grid network operation preventive control measures/ B8110C Power system control C7410B Power engineering computing |
中文摘要 | An improved OPA model is proposed. This model contains two layers of iteration. The inner iteration which describes the fast dynamic of the system considers the influence of the power flow, the dispatching, the automation, and the relay protection, etc, while the outer one which describes the long term slow dynamics of the system considers the impact from power grid upgrade, network operation, planning and other factors. Furthermore, based on the VaR and CVaR, a method which could be used to evaluate the blackout risk of the power system quantitatively is presented. Appropriate preventive control measures are proposed as well. The effectiveness of the improved OPA model is verified by the simulation results concerning the northeast power grid of China. |
语种 | 中文 |
出版者 | State Power Corporation of China ; China |
内容类型 | 期刊论文 |
源URL | [http://hdl.handle.net/123456789/82762] |
专题 | 清华大学 |
推荐引用方式 GB/T 7714 | Mei Shengwei,He Fei,Zhang Xuemin,et al. An improved OPA model and the evaluation of blackout risk[J],2010, 2010. |
APA | Mei Shengwei,He Fei,Zhang Xuemin,&Xia Deming.(2010).An improved OPA model and the evaluation of blackout risk.. |
MLA | Mei Shengwei,et al."An improved OPA model and the evaluation of blackout risk".(2010). |
个性服务 |
查看访问统计 |
相关权益政策 |
暂无数据 |
收藏/分享 |
除非特别说明,本系统中所有内容都受版权保护,并保留所有权利。
修改评论