Grounding system design method in high soil resistivity regions
Zhuang Chi-jie ; Zeng Rong ; Zhang Bo ; He Jin-liang
2010-10-12 ; 2010-10-12
关键词Practical/ earthing power grids substation protection/ grounding system design method high soil resistivity regions equipment protection substation grounding resistance voltage balancing unequal spacing grounding grid technology/ B8140 Power system protection B8375 Substations
中文摘要This paper analyzes the restriction of grounding system design based on the requirements of equipment safety and personal safety, and discusses the limitation of conventional design methods in high soil resistivity regions with a real engineering project. Thereafter, a design method that is not restricted by the grounding resistance limit of the existing regulation is proposed. The main principle of this method is to increase the allowed value of grounding resistance and strengthen the equipment protection. The maximal allowed value of substation grounding resistance is calculated according to the working parameters and equipment parameters, and the initial design scheme is verified and modified according to the requirements of step voltage and touch voltage to ensure personal safety. The grounding system structure is optimized on the principle of balancing-voltage, and the unequal spacing grounding grid technology and the explosion grounding technology are very effective. Meanwhile, the expenses on equipment protection should be increased to guarantee safe running. If the increased expenses on equipment protection are lower than the cost of decreasing grounding resistance, the whole project cost would be reduced and the grounding system can be designed both safely and economically. This method has been proved to be effective in engineering practice.
语种中文
出版者Editorial Board of High Voltage Engineering ; China
内容类型期刊论文
源URL[http://hdl.handle.net/123456789/82624]  
专题清华大学
推荐引用方式
GB/T 7714
Zhuang Chi-jie,Zeng Rong,Zhang Bo,et al. Grounding system design method in high soil resistivity regions[J],2010, 2010.
APA Zhuang Chi-jie,Zeng Rong,Zhang Bo,&He Jin-liang.(2010).Grounding system design method in high soil resistivity regions..
MLA Zhuang Chi-jie,et al."Grounding system design method in high soil resistivity regions".(2010).
个性服务
查看访问统计
相关权益政策
暂无数据
收藏/分享
所有评论 (0)
暂无评论
 

除非特别说明,本系统中所有内容都受版权保护,并保留所有权利。


©版权所有 ©2017 CSpace - Powered by CSpace