CORC  > 清华大学
Pollution flashover characteristics of the insulators of +/-800 kV HVDC lines under high altitude areas
Wang Xiang-peng ; Zhou Jun ; Wang Li-ming ; Guan Zhi-cheng
2010-10-12 ; 2010-10-12
关键词Practical Experimental/ flashover HVDC power transmission insulation testing insulator contamination power cable insulation/ pollution flashover HVDC line insulator high altitude area UHVDC transmission line artificial contamination tests salt deposit density voltage 800 kV/ B8130H Power line supports, insulators and connectors B8120G d.c. transmission B2810D Dielectric breakdown and discharges/ voltage 8.0E+05 V
中文摘要In order to research the flashover characteristics of the insulators for 800 kV UHVDC transmission line, the artificial contamination tests were carried out for different types of insulators under different pressures and in different typical kinds of equivalent salt deposit density (ESDD), and the test results were analyzed. The results show that the flashover voltage of polluted insulators regularly decreases with the increasing of the altitude. By comparing the withstand flashover performance of different types of insulator under different altitudes, the suggestions on insulator type selection for +800 kV UHVDC transmission lines are put forward.
语种中文
出版者Editorial Board of High Voltage Engineering ; China
内容类型期刊论文
源URL[http://hdl.handle.net/123456789/82498]  
专题清华大学
推荐引用方式
GB/T 7714
Wang Xiang-peng,Zhou Jun,Wang Li-ming,et al. Pollution flashover characteristics of the insulators of +/-800 kV HVDC lines under high altitude areas[J],2010, 2010.
APA Wang Xiang-peng,Zhou Jun,Wang Li-ming,&Guan Zhi-cheng.(2010).Pollution flashover characteristics of the insulators of +/-800 kV HVDC lines under high altitude areas..
MLA Wang Xiang-peng,et al."Pollution flashover characteristics of the insulators of +/-800 kV HVDC lines under high altitude areas".(2010).