Analysis of grading ring configuration for composite insulators on transmission tower
Zhang Bo ; He Jin-liang ; Zeng Rong ; Zhu Pu-xuan ; Zhu Pu-xuan
2010-10-12 ; 2010-10-12
关键词Practical Theoretical or Mathematical/ boundary-elements methods composite insulators method of moments poles and towers/ grading ring configuration analysis composite insulator transmission tower electric field strength boundary-element method moment method electric-field distribution heterogeneous media voltage 330 kV/ B8130H Power line supports, insulators and connectors B0290T Finite element analysis/ voltage 3.3E+05 V
中文摘要In order to reduce the electric field strength at the insulator ends, grading rings are installed at the ends of insulators. In this paper, a model coupling the indirect boundary-element method to the moment method is developed to calculate the electric-field distribution around the composite insulators at the heads of transmission towers. The heterogeneous media, such as the composite insulators and the filament metal structures such as the transmission towers and the transmission lines, are considered altogether. The effect of the grading ring on the electric fields a- long the insulator and on the surface of the grading ring is analyzed on the basis of the calculated results on the composite insulators of a 330 kV transmission tower. Analysis results show that increasing the diameter of the grading ring's tube or reducing the diameter of the grading ring can reduce the maximum electric field at the insulator's high voltage end and the maximum electric field on the surface of the grading ring. At the same time, the maximum electric field at the insulator's high voltage end will increase first and then decrease with increasing the shielding depth of the grading ring.
语种中文
出版者Editorial Board of High Voltage Engineering ; China
内容类型期刊论文
源URL[http://hdl.handle.net/123456789/82358]  
专题清华大学
推荐引用方式
GB/T 7714
Zhang Bo,He Jin-liang,Zeng Rong,et al. Analysis of grading ring configuration for composite insulators on transmission tower[J],2010, 2010.
APA Zhang Bo,He Jin-liang,Zeng Rong,Zhu Pu-xuan,&Zhu Pu-xuan.(2010).Analysis of grading ring configuration for composite insulators on transmission tower..
MLA Zhang Bo,et al."Analysis of grading ring configuration for composite insulators on transmission tower".(2010).
个性服务
查看访问统计
相关权益政策
暂无数据
收藏/分享
所有评论 (0)
暂无评论
 

除非特别说明,本系统中所有内容都受版权保护,并保留所有权利。


©版权所有 ©2017 CSpace - Powered by CSpace