CORC  > 清华大学
Response Coefficient: A New Concept to Evaluate Ventilation Performance with "Pulse'' Boundary Conditions
Li, Xianting ; Zhu, Fenfei
2010-10-12 ; 2010-10-12
关键词indoor air quality (IAQ) ventilation efficiency passive contaminant air distribution evaluation index COMPUTATIONAL FLUID-DYNAMICS AIR ACCESSIBILITY PREDICTION Construction & Building Technology Engineering, Environmental Public, Environmental & Occupational Health
中文摘要Releasing a "pulse'' tracer contaminant at a given point, either in the air supply or in the indoor space, and monitoring its transient distribution in a steady-state flow field, allows the performance of the air distribution to be evaluated. Two nondimensional indices have been defined, Response Coefficient to Supply Air (RCSA) and Response Coefficient to Contaminant Source (RCCS), to characterize spatial and temporal distribution under different air distribution patterns. To demonstrate their characteristics a 2D ventilated room was numerically analyzed. The results show that RCSA at each location (except the inlet) and RCCS at each location in the room (except the contaminant source) initially increase, then decrease, and become zero when time is long enough; RCSA "records'' the characteristics of the flow field. There will be only one maximum response coefficient value under a piston flow field, while under a flow field with recirculation, there will be several, which may be used to evaluate the airflow pattern; RCCS contains information on the contaminant source position under a specific flow field. The relative positions of the contaminant source and the monitoring points determine response curves, which may be used to judge the position of a contaminant source; accumulation of RCSA and RCCS will become constant when time is long enough. The accumulation value of RCSA at any location indoors is 1, while accumulation values of RCCS at different locations differ from each other, but are determined by the relative position of the contaminant source and the location.
语种英语 ; 英语
出版者SAGE PUBLICATIONS LTD ; LONDON ; 1 OLIVERS YARD, 55 CITY ROAD, LONDON EC1Y 1SP, ENGLAND
内容类型期刊论文
源URL[http://hdl.handle.net/123456789/80687]  
专题清华大学
推荐引用方式
GB/T 7714
Li, Xianting,Zhu, Fenfei. Response Coefficient: A New Concept to Evaluate Ventilation Performance with "Pulse'' Boundary Conditions[J],2010, 2010.
APA Li, Xianting,&Zhu, Fenfei.(2010).Response Coefficient: A New Concept to Evaluate Ventilation Performance with "Pulse'' Boundary Conditions..
MLA Li, Xianting,et al."Response Coefficient: A New Concept to Evaluate Ventilation Performance with "Pulse'' Boundary Conditions".(2010).
个性服务
查看访问统计
相关权益政策
暂无数据
收藏/分享
所有评论 (0)
暂无评论
 

除非特别说明,本系统中所有内容都受版权保护,并保留所有权利。


©版权所有 ©2017 CSpace - Powered by CSpace