500kV港城变电站外绝缘放电原因分析
刘平原 ; 王黎明 ; 何宏明 ; LIU Pingyuan ; WANG Liming ; HE Hongming
2010-06-07 ; 2010-06-07
关键词外绝缘 电场 含糖污秽 防污闪涂料 均压环 external insulation electric-field sugar-containing contamination anti-pollution coating corona ring TM63
其他题名Analysis on Contamination Discharges of External Insulation in 500 kV Gangcheng Substation
中文摘要通过绝缘子表面污秽状况调查、人工污秽试验和电场计算来分析500kV港城变电站外绝缘严重放电的原因,认为港城站设备上附着有含糖污秽,导致外绝缘某些区域电场增强,从而引起比较强烈和普遍的放电现象。以人工污秽试验研究了含糖污秽与不含糖污秽的放电机理,同时探讨防污闪涂料对于削弱港城站外绝缘放电的效果和长期性能。文章还基于电场计算结果提出了改善电场分布的均压环参数选择建议。; The cause of serious discharges of external insulation in 500 kV Gangcheng Substation is analyzed through of insulator surface contaminations surveys, artifical cantamination laboratory tests and the electric-field calculations, and it is concluded that sugar-containing contaminations attached to the equipments in the substation result in the electric-field increase of some regions of the external-insulation surfaces, and thus lead the strong and widespread discharge.The discharge mechanism of the sugar-containing and non sugar-containing contaminations are studied with artifical cantamination laboratory tests, at the same time the effect and long-term performance of the anti-pollution coating to weaken the external-insulation discharges in the substation are discussed too.Based on the electric-field calculation results, this paper proposes some suggestions for the corona ring parameters selection of the insulator strings to improve the electric-field distribution.
语种中文 ; 中文
内容类型期刊论文
源URL[http://hdl.handle.net/123456789/45063]  
专题清华大学
推荐引用方式
GB/T 7714
刘平原,王黎明,何宏明,等. 500kV港城变电站外绝缘放电原因分析[J],2010, 2010.
APA 刘平原,王黎明,何宏明,LIU Pingyuan,WANG Liming,&HE Hongming.(2010).500kV港城变电站外绝缘放电原因分析..
MLA 刘平原,et al."500kV港城变电站外绝缘放电原因分析".(2010).
个性服务
查看访问统计
相关权益政策
暂无数据
收藏/分享
所有评论 (0)
暂无评论
 

除非特别说明,本系统中所有内容都受版权保护,并保留所有权利。


©版权所有 ©2017 CSpace - Powered by CSpace