CORC  > 清华大学
±500kV换流站交流侧刀闸操作对直流侧二次系统电磁干扰分析
曾嵘 ; 余占清 ; 傅闯 ; 黄莹 ; 何金良 ; 李伟 ; 冯鸫 ; ZENG Rong ; YU Zhan-qing ; FU Chuang ; HUANG Ying ; HE Jin-liang ; LI Wei ; FENG Dong
2010-05-12 ; 2010-05-12
关键词高压直流输电 电磁干扰 操作暂态 交流隔离开关 直流二次系统 HVDC EMI switching transient AC isolator DC side secondary systems TM63
其他题名Analysis on EMI from Switching Transient in AC Side into Secondary Systems in DC Side of �00 kV HVDC Converter Stations
中文摘要注意到换流站交流侧隔离开关和断路器操作会产生电磁骚扰,且最近该类骚扰源造成了多起直流闭锁事故。现场测量了开关操作产生的电磁骚扰,总结了骚扰源的基本特性,比较了不同类型开关操作产生的暂态过程的差异。采用实验的方法分析了不同的系统工作状态下的传播机理。分析了该类骚扰在二次系统中的分布以及时域和频域特性。基于离线实验分析了直流分流器的高频特性。; Noticing that transient EMI is generated by operating isolators and circuit-breakers in the AC side of HVDC converter stations, and resulting recently in several trips in several �00 kV HVDC converter stations, characteristics of transient electromagnetic interference due to different types of switching operations are summarized and compared based on onsite tests in a practical converter station. Measurements are performed to analyze the propagation mechanism of transient processes of various switching operations during different operation status. The EM noises generated by switching operations into secondary systems, especially the measuring system in DC side are analyzed as well. The high frequency characteristics of DC shunts, which is the most important path for EM noise propagating, is also analyzed based on tests.
语种中文 ; 中文
内容类型期刊论文
源URL[http://hdl.handle.net/123456789/29258]  
专题清华大学
推荐引用方式
GB/T 7714
曾嵘,余占清,傅闯,等. ±500kV换流站交流侧刀闸操作对直流侧二次系统电磁干扰分析[J],2010, 2010.
APA 曾嵘.,余占清.,傅闯.,黄莹.,何金良.,...&FENG Dong.(2010).±500kV换流站交流侧刀闸操作对直流侧二次系统电磁干扰分析..
MLA 曾嵘,et al."±500kV换流站交流侧刀闸操作对直流侧二次系统电磁干扰分析".(2010).
个性服务
查看访问统计
相关权益政策
暂无数据
收藏/分享
所有评论 (0)
暂无评论
 

除非特别说明,本系统中所有内容都受版权保护,并保留所有权利。


©版权所有 ©2017 CSpace - Powered by CSpace