CORC  > 清华大学
Analytical solution of adiabatic heat and mass transfer process in packed-type liquid desiccant equipment and its application
Chen, X. Y. ; Li, Z. ; Jiang, Y. ; Qu, K. Y.
2010-05-10 ; 2010-05-10
会议名称SOLAR ENERGY ; Eurosun 2004 Conference ; Freiburg, GERMANY ; Web of Science
关键词liquid desiccant heat and mass transfer analytical solution AIR DEHUMIDIFICATION SYSTEM MODEL REGENERATION Energy & Fuels
中文摘要This paper presents an integrated analytical solution of adiabatic heat and mass transfer in packed-type liquid desiccant equipment based on proposed mathematical models in both parallel-flow and counter-flow configurations. In the derivation process, the desiccant concentration at the inlet and outlet of the absorber is assumed to be constant. That means this solution is suitable for high desiccant flow rate conditions. This analytical solution has good accuracy when compared with reliable experimental data available in the literature. The moisture removal rate is derived from this solution and every factor that influences performance can be easily analyzed. Another benefit is that it can be used to discover the optimum air-to-solution flow rate ratio with which the driving force may be kept constant throughout the column. The optimum flow rate ratio may be used for optimal system design and to realize a reversible heat and mass transfer process. (c) 2006 Elsevier Ltd. All rights reserved.
会议录出版者PERGAMON-ELSEVIER SCIENCE LTD ; OXFORD ; THE BOULEVARD, LANGFORD LANE, KIDLINGTON, OXFORD OX5 1GB, ENGLAND
语种英语 ; 英语
内容类型会议论文
源URL[http://hdl.handle.net/123456789/19758]  
专题清华大学
推荐引用方式
GB/T 7714
Chen, X. Y.,Li, Z.,Jiang, Y.,et al. Analytical solution of adiabatic heat and mass transfer process in packed-type liquid desiccant equipment and its application[C]. 见:SOLAR ENERGY, Eurosun 2004 Conference, Freiburg, GERMANY, Web of Science.
个性服务
查看访问统计
相关权益政策
暂无数据
收藏/分享
所有评论 (0)
暂无评论
 

除非特别说明,本系统中所有内容都受版权保护,并保留所有权利。


©版权所有 ©2017 CSpace - Powered by CSpace