CORC  > 清华大学
Calculation of total electric field and ionic current density of double-circuit HVDC transmission lines
Tian Ji-huan ; Zou Jun ; Liu Jie ; Yuan Jian-sheng
2010-05-06 ; 2010-05-06
关键词Practical/ HVDC power transmission power transmission lines/ total electric field ionic current density double-circuit HVDC transmission lines electromagnetic environment/ B8120G d.c. transmission
中文摘要In China there are still not experiences in the design and operation of double-circuit HVDC transmission lines. For this reason, the authors calculate the total electric field and ionic current density caused by corona effect of double-circuit HVDC transmission lines, and analyze the impacts of different conductor configurations and structural parameters such as conductor inter-spacing, line height to ground, number of sub-conductors and conductor radius, on ground ionic current density and field strength. Calculation results show that the ground total electric field strength and the ionic current density is smaller while the two transmission lines are configured vertically; under the same conductor dimension and line height, the ground field strength of rationally configured double-circuit transmission lines is far less than that of single-circuit transmission line; the smaller is the double-circuit lines' vertical inter-spacing, the less are the ground field strength and ionic current; in addition, the electromagnetic environment of double-circuit HVDC transmission lines is superior to that of single-circuit transmission line.
语种中文 ; 中文
出版者Electric Power Research Institute ; China
内容类型期刊论文
源URL[http://hdl.handle.net/123456789/11747]  
专题清华大学
推荐引用方式
GB/T 7714
Tian Ji-huan,Zou Jun,Liu Jie,et al. Calculation of total electric field and ionic current density of double-circuit HVDC transmission lines[J],2010, 2010.
APA Tian Ji-huan,Zou Jun,Liu Jie,&Yuan Jian-sheng.(2010).Calculation of total electric field and ionic current density of double-circuit HVDC transmission lines..
MLA Tian Ji-huan,et al."Calculation of total electric field and ionic current density of double-circuit HVDC transmission lines".(2010).
个性服务
查看访问统计