Test of fault line selector based on current traveling wave | |
Kong Rui-zhong ; Dong Xin-zhou ; Bi Jian-guang | |
2010-05-06 ; 2010-05-06 | |
关键词 | Practical/ current transformers earthing electric resistance fault location power distribution faults power distribution protection relay protection/ fault line selector current traveling wave protection distribution systems transient relay testing device high-speed sampling current transformer configurations neural grounded systems fault resistances/ B8120J Distribution networks B8140C Protection apparatus B8350 Transformers and reactors |
中文摘要 | In order to verify the correctness of the principle and functions of fault line selector based on current traveling wave, this paper reports the results of tests under all kinds of really grounded fault conditions in distribution systems simulated by transient relay testing device. Those tests include high-speed sampling and communication, selecting the exact fault line and alarming under different current transformer configurations, different ways of neural grounded systems, and different fault resistances. Results show that the principle of the device is correct and its functions meet the requirement of design. |
语种 | 中文 ; 中文 |
出版者 | State Power Corp. of China ; China |
内容类型 | 期刊论文 |
源URL | [http://hdl.handle.net/123456789/11520] |
专题 | 清华大学 |
推荐引用方式 GB/T 7714 | Kong Rui-zhong,Dong Xin-zhou,Bi Jian-guang. Test of fault line selector based on current traveling wave[J],2010, 2010. |
APA | Kong Rui-zhong,Dong Xin-zhou,&Bi Jian-guang.(2010).Test of fault line selector based on current traveling wave.. |
MLA | Kong Rui-zhong,et al."Test of fault line selector based on current traveling wave".(2010). |
个性服务 |
查看访问统计 |
相关权益政策 |
暂无数据 |
收藏/分享 |
除非特别说明,本系统中所有内容都受版权保护,并保留所有权利。
修改评论