Influence of volumetric-flow rate in the crystallizer on the gas-hydrate cool-storage process in a new gas-hydrate cool-storage system
Bi, YH; Guo, TW; Zhu, TG; Fan, SS; Liang, DQ; Zhang, L
刊名applied energy
2004-05-01
卷号78期号:1页码:111-121
关键词cool-storage process gas hydrate experimental study cold-energy stored volumetric flow rate in the crystallizer
英文摘要experimental results of the gas-hydrate r141b cool-storage process are used to study the performance of a new type gas-hydrate cool-storage system. the relations among the cooling rate of the cool-storage medium, the degree of subcooling of crystallization, the formation rate of gas-hydrate, the cold energy stored and the volumetric flow rate in the crystallizer are provided. the experimental results indicate that the cool storage effect of the system is better when the volumetric flow rate in the crystallizer is between 150 and 450 l/h, the corresponding cooling rate of the cool-storage medium is between 0.055 and 0.105 degreesc/min, the degree of subcooling of crystallization is between 1.97 and 3.50 degreesc, the formation rate of the gas-hydrate is between 0.30 and 0.4 g/s, and the cold energy stored is between 2.9 and 4.0 mj. the results presented provide guidance for the actual efficient operation of a new type of gas-hydrate cool-storage system. (c) 2003 elsevier ltd. all rights reserved.
WOS标题词science & technology ; technology
类目[WOS]energy & fuels ; engineering, chemical
研究领域[WOS]energy & fuels ; engineering
关键词[WOS]behavior ; water
收录类别SCI
语种英语
WOS记录号WOS:000220291000008
内容类型期刊论文
源URL[http://ir.giec.ac.cn/handle/344007/10483]  
专题中国科学院广州能源研究所
作者单位1.Chinese Acad Sci, Tech Inst Phys & Chem, Grad Sch, Beijing 100080, Peoples R China
2.Beijing Univ Technol, Inst Civil & Architecture Engn, Beijing 100022, Peoples R China
3.Chinese Acad Sci, Guangzhou Inst Energy Convers, Guangzhou 510070, Peoples R China
推荐引用方式
GB/T 7714
Bi, YH,Guo, TW,Zhu, TG,et al. Influence of volumetric-flow rate in the crystallizer on the gas-hydrate cool-storage process in a new gas-hydrate cool-storage system[J]. applied energy,2004,78(1):111-121.
APA Bi, YH,Guo, TW,Zhu, TG,Fan, SS,Liang, DQ,&Zhang, L.(2004).Influence of volumetric-flow rate in the crystallizer on the gas-hydrate cool-storage process in a new gas-hydrate cool-storage system.applied energy,78(1),111-121.
MLA Bi, YH,et al."Influence of volumetric-flow rate in the crystallizer on the gas-hydrate cool-storage process in a new gas-hydrate cool-storage system".applied energy 78.1(2004):111-121.
个性服务